Final-year projects / Agriculture

Pump motor protection: voltage, overload and dry run

Farm pump motors burn out from low voltage, overloads and running dry, and rewinding costs thousands. A protection unit that checks voltage and current and trips the motor before damage saves farmers money.

Arduino UnoMini or Major projectEEE, EIE, Diploma
UNOVOLTAGCTON4.65 VFeatured
Parts
₹3,425
Build
12 weeks
Board
Arduino Uno
Objectives
6
Demonstrate on the lab bench with a small motor, and switch real pumps only through a rated contactor fitted by an electrician.

Block diagram

Inputs
  • VOLTAG
    Voltage sensorChecks under and over voltage
  • CT
    CT sensorMeasures motor current
Controller
  • UNO
    Arduino UnoRuns the protection logic
Outputs
  • ON
    Relay to contactor coilTrips the motor
  • 23.4°CLCD
    LCD and buzzerShow the fault
  • 4G
    4G modemSends SMS alerts and calls over the mobile network+
  • CLOUD
    Cloud dashboardStores readings, plots trends and sends alerts+

Objectives

  1. To measure supply voltage and motor current as true RMS.
  2. To trip on under voltage (below 180 V) and over voltage (above 260 V) after a delay.
  3. To trip on overload with an inverse-time curve, and on dry run (current below 60% of normal).
  4. To restart automatically after voltage recovers, with a set delay.
  5. To send SMS alerts through a 4G modem where no Wi-Fi is available.
  6. To publish readings over MQTT and show them on a live dashboard with threshold alerts.

Parts and specifications

Total about ₹3,425 at typical online prices. Tap a part for its pinout and datasheet notes.

Design calculations

Voltage limits

Trip below 180 V or above 260 V for more than 5 s (to ride through brief dips); restart when 195 to 250 V holds for 2 minutes.

Inverse-time overload

Trip time t = k / ((I/In)² − 1). With k = 60 s: 1.5 × In trips in 48 s, 2 × In in 20 s, 6 × In (locked rotor) in under 2 s.

Dry run

A pump running dry draws much less current. Learn normal current over the first 2 minutes; trip if it falls below 60% of that for 10 s.

Restart delay

Wait 2 minutes after a trip so the water column settles and the motor cools before restarting.

Pin map

SignalPin or connection
ZMPT101B OUTA0
SCT-013 (biased 2.5 V)A1
Relay to contactor coilD7
BuzzerD8
LCDA4 / A5
Reset buttonD2

Firmware outline

  1. Sample voltage and current at 2 kHz, compute RMS every 200 ms.
  2. Check under/over voltage timers.
  3. Integrate overload heat: add (I/In)² − 1 each tick, trip when the total reaches k.
  4. Detect dry run against learned normal current.
  5. On trip, open the relay, show the cause and log it; restart after the delay if the cause is gone (not after overload, which needs a manual reset).

Test plan

TestExpected result
Voltage lowered with a variac (guide present)Trips below 180 V after 5 s
Motor shaft loadedOverload trip time matches the curve
Fan with blades removed (light load)Dry-run trip
Voltage restoredAuto restart after 2 minutes

These rows start your results table when you plan the project.

Viva practice

Say your answer out loud first, then check. The first 2 answers are free; Maker opens all 5.

1. Why does low voltage damage motors?
2. What is an inverse-time curve?
3. Why does a dry pump draw less current?
4. Why switch a contactor and not the motor directly?
5. Why not restart at once after a trip?

Make it yours

One or two upgrades for a mini project, two to four for a major one.

Build these first

Datasheets and sources to cite

  • IS/IEC 60947-4-1 (contactors and motor starters)
  • IS 8034 (submersible pumpsets)
  • YHDC SCT-013 datasheet

About this project

How much does the pump motor protection: voltage, overload and dry run project cost?

About ₹1,835 for the parts in the base list: Arduino Uno R3 (CH340 clone), ZMPT101B AC voltage sensor, SCT-013-030 split-core CT, 5 V relay module (1 channel), 16×2 LCD with I²C backpack, Active buzzer 5 V, Small single-phase motor or fan as the test load, Closed box, fuse and MCB.

How long does it take?

About 8 weeks for the base project, built on an Arduino Uno. Each upgrade adds time.

Which branches is it suitable for?

Electrical and Electronics, Instrumentation, Diploma (any electronics branch), as a mini or major project.

Which pins and design calculations does it use?

ZMPT101B OUT on A0; SCT-013 (biased 2.5 V) on A1; Relay to contactor coil on D7. Worked calculations on this page: voltage limits, inverse-time overload, dry run, restart delay.

How do I test it?

Voltage lowered with a variac (guide present): Trips below 180 V after 5 s. Motor shaft loaded: Overload trip time matches the curve. Fan with blades removed (light load): Dry-run trip. Voltage restored: Auto restart after 2 minutes.

What are the objectives?

To measure supply voltage and motor current as true RMS. To trip on under voltage (below 180 V) and over voltage (above 260 V) after a delay. To trip on overload with an inverse-time curve, and on dry run (current below 60% of normal). To restart automatically after voltage recovers, with a set delay.