Final-year projects / Power systems

Distribution transformer health monitor

Distribution transformers fail from overload and overheating, cutting power to whole streets for days. A monitor that tracks load current, voltage, oil temperature and oil level and alerts the utility early can prevent many failures.

ESP32Major projectEEE, EIE, ECE
ESP32CTVOLTAGOIL24.4°CFeatured
Parts
₹4,140
Build
14 weeks
Board
ESP32
Objectives
5
Use a small low-voltage test transformer in the lab. Never approach a utility transformer, which is high-voltage equipment.

Block diagram

Inputs
  • CT
    CT sensorMeasures load current
  • VOLTAG
    Voltage sensorMeasures secondary voltage
  • OIL
    Oil temperature probeMeasures top-oil temperature
  • Oil level floatDetects a leak
Controller
  • ESP32
    ESP32Works out load and hot-spot risk
Outputs
  • 4G
    4G or Wi-Fi alertTells the utility
  • ON
    Cooling fan relayStarts forced cooling
  • 4G
    4G modemSends SMS alerts and calls over the mobile network+

Objectives

  1. To measure load current, voltage and percent loading against the rating.
  2. To measure top-oil temperature and estimate hot-spot rise.
  3. To start cooling and raise an alert on overload, high temperature or low oil.
  4. To log a day of readings on the test transformer.
  5. To send SMS alerts through a 4G modem where no Wi-Fi is available.

Parts and specifications

Total about ₹4,140 at typical online prices. Tap a part for its pinout and datasheet notes.

Design calculations

Percent loading

Rated secondary current of the test unit 2 A. Measured 1.7 A RMS → 85% load.

True RMS

Sample at 2 kHz for 200 ms (10 cycles): Irms = √(Σi² / N). It handles distorted current from electronic loads.

Hot-spot estimate (IEC 60076-7 style)

Hot spot ≈ top oil + H × gr × K^y. With top oil 70 °C, H = 1.3, gr = 23 K, K = 0.85, y = 1.6: 70 + 1.3 × 23 × 0.77 ≈ 93 °C.

Ageing

Insulation ageing roughly doubles for each 6 °C above 98 °C hot spot, so short overloads matter less than long ones.

Pin map

SignalPin or connection
SCT-013 (biased at 1.65 V)GPIO 34
ZMPT101B OUTGPIO 35
DS18B20 probes (top oil, ambient)GPIO 4
Oil level floatGPIO 27 (pull-up)
Fan relayGPIO 26
OLEDGPIO 21 / 22

Firmware outline

  1. Every 10 s compute Irms and Vrms from 10 cycles of samples.
  2. Read top-oil and ambient temperatures every minute.
  3. Compute load %, hot-spot estimate and a health state.
  4. Start the fan above 80% load or 65 °C; alert at 110% load, 85 °C, or low oil.
  5. Send readings to the dashboard; keep a 24 h log.

Test plan

TestExpected result
Load stepped 25, 50, 75, 100%Current vs clamp meter within 3%
Supply voltage via variac (with guide)Voltage tracks within 2%
Probe warmed in hot waterFan starts, then alert
Float liftedLow-oil alert

These rows start your results table when you plan the project.

Viva practice

Say your answer out loud first, then check. The first 2 answers are free; Maker opens all 5.

1. Why do transformers fail?
2. What is top-oil vs hot-spot temperature?
3. Why true RMS?
4. How does the ZMPT101B isolate mains?
5. What else do utilities monitor?

Make it yours

One or two upgrades for a mini project, two to four for a major one.

Build these first

Datasheets and sources to cite

  • IS 2026 (power transformers)
  • IEC 60076-7 loading guide for oil-immersed transformers
  • YHDC SCT-013 datasheet

About this project

How much does the distribution transformer health monitor project cost?

About ₹2,550 for the parts in the base list: ESP32 DevKit V1, SCT-013-030 split-core CT, ZMPT101B AC voltage sensor, DS18B20 waterproof probe × 2, Vertical float switch, 5 V relay module (1 channel), 12 V DC fan 80 mm, 0.96 inch OLED (SSD1306, I²C), Small 230/12 V 2 A transformer as the test unit, with a load, Box, fuse and terminal strip.

How long does it take?

About 12 weeks for the base project, built on an ESP32. Each upgrade adds time.

Which branches is it suitable for?

Electrical and Electronics, Instrumentation, Electronics and Communication, as a major project.

Which pins and design calculations does it use?

SCT-013 (biased at 1.65 V) on GPIO 34; ZMPT101B OUT on GPIO 35; DS18B20 probes (top oil, ambient) on GPIO 4. Worked calculations on this page: percent loading, true rms, hot-spot estimate (iec 60076-7 style), ageing.

How do I test it?

Load stepped 25, 50, 75, 100%: Current vs clamp meter within 3%. Supply voltage via variac (with guide): Voltage tracks within 2%. Probe warmed in hot water: Fan starts, then alert. Float lifted: Low-oil alert.

What are the objectives?

To measure load current, voltage and percent loading against the rating. To measure top-oil temperature and estimate hot-spot rise. To start cooling and raise an alert on overload, high temperature or low oil. To log a day of readings on the test transformer.