AC, RMS and Real Power: the short answer
Alternating current changes direction many times a second. Indian mains is 230 V at 50 Hz.
- Level
- Advanced
- Time
- About 6 min
- Topic
- Basics
Work with AC and PWM using RMS values, and calculate real power including power factor.
Before this: Ohm’s Law, Power & Heat, PWM Timing & Actuator Interfaces
Alternating current changes direction many times a second. Indian mains is 230 V at 50 Hz. The 230 V is an RMS (root mean square) value: the DC voltage that would heat a resistor by the same amount. For a sine wave the peak is √2 times the RMS, so mains actually swings between +325 V and −325 V. Components connected to mains must be rated for the peak, and a 230 V circuit is lethal; build and measure only low-voltage circuits unless you are trained.
RMS matters for any waveform that is not steady DC, including PWM. A PWM signal switching between 0 and V with duty cycle D has an average of D × V but an RMS of √D × V. Heating, and so the power in a resistive load such as a heater or an LED resistor, follows the RMS, not the average. Multimeters on DC show the average; only a true-RMS meter on AC gives the RMS of a non-sine waveform.
With AC loads that contain motors or power supplies, current and voltage are not in step. Real power (watts) is P = Vrms × Irms × PF, where the power factor PF is between 0 and 1. The product Vrms × Irms is the apparent power in volt-amperes (VA). Wires, fuses and UPS ratings must handle the VA, while the electricity bill counts the watts.
RMS is the heating value
RMS is the steady DC voltage that would heat a resistor as much as the AC does. For a sine wave it is the peak divided by 1.41, so a 325 V peak is 230 V RMS. A different wave shape has a different ratio, and a meter that assumes a sine reads a chopped or distorted wave wrongly. A true-RMS meter calculates the actual value.
The crest factor is peak divided by RMS. A sine has 1.41, but a spiky load current can have a much higher one, which matters for choosing meters, fuses and supplies.
Real, apparent and reactive power
Apparent power in volt-amperes is RMS voltage times RMS current. Real power in watts is what does work, and it is smaller when the current and voltage are out of step. The power factor is real power divided by apparent power. A motor or a transformer with an inductive load draws current that lags the voltage, so it needs more current than its watts suggest.
A 230 V load of 100 W at a power factor of 0.5 draws about 0.87 A, not 0.43 A, so wiring and a supply must be sized for the current.
Measuring mains safely
Do not probe mains directly. Use an isolated measurement such as a certified energy meter module, or a current transformer with a built-in burden, and keep mains wiring inside an enclosure built for it.
- Reading a distorted wave with a meter that is not true-RMS.
- Sizing wiring by watts and ignoring power factor.
- Probing mains with an ordinary oscilloscope that is grounded.
- Vrms = Vpeak ÷ √2
- for a sine wave
- P = Vrms × Irms × cos φ
- real power with phase angle φ